TH3015 transformer partial discharge online monitoring

Product Description

The TH3015 transformer partial discharge online monitoring system employs the signal sensing technology, anti-interference technology and advanced computer analysis method for online monitoring of transformer partial discharge. The system adopts ultrasonic, UHF and high-frequency current electric acoustic partial discharge detection technology to achieve partial discharge monitoring, which can realize analysis of discharge information such as the maximum discharge amount, discharge phase, discharge times, and average discharge amount of the main transformer UHF partial discharge.

Scope of Application

It is applicable to partial discharge monitoring of oil-immersed transformers at all voltage levels in substation.
TH3015 变压器局放在线监测系统.png

Technical Features/Advantages

Comprehensive data analysis

It has the functions of real-time acquisition, storage and analysis of partial discharge data of transformer equipment, and can display the peak value diagram, discharge times-phase diagram, peak value-discharge times-phase spectrum, peak-cycle-phase spectrum of partial discharge in real time, which is convenient for users to carry out real-time analysis of data, and it is simple and intuitive.

Strong anti-interference performance

By using the ultrasonic, ultra-high frequency and high-frequency current electric acoustic partial discharge detection technology, it is not affected by corona interference and can avoid the interference of communication signals.

Interference suppression in hardware circuit

Using multiple anti-interference technologies, current structures such as noise filtering channel and noise acquisition channel are adopted in the hardware design, which are used to filter on-site noise and purify the acquisition signal.

Flexible communication

It supports multiple protocols and the IEC61850 communication, and it can be connected to the digital substation monitoring system.

High reliability

Parameters, such as partial discharge action level and standard density, can be set via software to automatically separate noise interference signals and improve the reliability of detection results.

Friendly system interface

The system is easy to operate, which has the functions of data analysis and diagnosis, analysis and prediction according to historical trends, as well as rich image display functions.

Specifications/Submodels

Ultrasonic sensor

No.

Parameter

Scope

1

Ultrasonic frequency range

20kHz~300 kHz

2

Type of ultrasonic detection channel interface

Waterproof connector

3

Minimum detection amount of ultrasonic sensor partial discharge

No less than 20pC

UHF sensor

No.

Parameter

Scope

1

UHF band range

300MHz-1500MHz

2

UHF sensitivity (equivalent height)

10mm

3

Input impedance of UHF detection channel

50Ω

4

Interface type of UHF detection channel

Waterproof connector

High-frequency sensor

No.

Parameter

Scope

1

Bandwidth of high frequency current sensor

50kHz~50MHz

2

Interface type of high frequency current detection channel

Waterproof connector

Acquisition unit parameters

No.

Parameter

Scope

1

Maximum sampling rate of the measurement host

≥20MS/s

2

Sampling data precision of measurement host

≥12位

≥12 bit

3

Synchronization function

It can obtain the power frequency synchronization signal from the 200VAC electric supply on the power socket, and power synchronization is adopted.

4

Working power supply

AC220±10%, 50±1Hz

5

Protection level

IP56, it can be used in the weather conditions of rain and snow.