TH3011 SF6 density minim moisture monitoring system
TH3011 SF6 density minim moisture monitoring system
Product Description
Scope of Application
Technical Features/Advantages
The product adopts advanced sensor technology, single-chip technology, communication technology, and modern physical analysis and control theory. Combining multiple independent intellectual properties and innovative technologies, this device can simultaneously monitor density, minim moisture and temperature of SF6 gases. It is composed of sensors and the host.
The monitor is connected to the SF6 gas chamber, and the host provides power to the monitor. Onsite display and communication transfer are realized, and it is transmitted to the background integrated automation system through the RS-485 bus.
Users can also choose to install the company's special background and monitoring software, which can be transferred to various wired or wireless networks.
Specifications/Submodels
No. | Technical index item | TH3011-WD minim moisture comprehensive monitor | TH3011-MD density comprehensive monitor |
1 | Function | It provides online monitoring of SF6 gas minim moisture, density and temperature, and power supply, on-site display and communication are transferred through the TH3011-WY or TH3011-WS host. | It provides online monitoring of SF6 gas density and temperature, and power supply, on-site display and communication are transferred through the TH3011-WY or TH3011-WS host. |
2 | Humidity measurement range | 1~2,000 μL/L (ppmv) | |
3 | Humidity measurement precision | ≤ ± 4% (FS) | |
4 | Humidity alarm threshold | Set at any value | |
5 | Humidity response speed | <10s | |
6 | Humidity measurement resolution | 1µL/L (ppmv) | |
7 | Density measurement range | 0.01~1.20 MPa | |
8 | Density measurement precision | ≤±0.5% (FS) | |
9 | Density measurement resolution | 0.01Mpa | |
10 | Density measurement precision | ≤ ±0.5% (FS) | |
11 | Density alarm blocking signal | Set according to user's requirements | |
12 | Temperature measurement precision | ±0.1℃ | |
13 | Communication interface and speed | RS-485 bus; 2,400 bps (can be transferred to various wired or wireless networks) | |
14 | Power voltage | DC24 | |
15 | Working environment | 0.10~1.00 MPa; -50 ℃~+55 ℃; ≤95%RH | |
16 | Standard gas interface | M30×2 thread (can be customized, connect air supplement port or air measurement port via three-way pipe) |