PRS-7367 Protection and Control Unit

Product Description

The PRS-7367 is a numerical distributed protection intended for protecting and monitoring various primary apparatus including overhead line, underground cable, transformer, capacitor, etc.

Scope of Application

The PRS-7367 is a numerical distributed protection intended for protecting and monitoring various primary apparatus including overhead line, underground cable, transformer, capacitor, etc. PRS-7367 can be used in various voltage level, generally ranging from 10kV to 35kV. PRS-7367 can detect and clear all types of internal phase-to-phase.

PRS-7367 provides fast and selective protection, monitoring and control for feeders and capacitors. The relay can operate correctly over a wide frequency range in order to accommodate power system frequency variations during disturbances.

This relay can sample the analog values from the traditional instrument transformers, or receive the sampled values from the electronic current and voltage transformers (via a merging unit). The binary inputs and outputs of this relay can be configured according to the demands of a practical engineering through the PRS IED Studio configuration tool auxiliary software, which can meet some special requirements of protection and control functions.

This relay can fully support the IEC61850 communication protocol and GOOSE function, and can completely meet the demands of a modern digitalized substation.

PRS-7367 6U三分之一层装置斜视图.png

Technical Features/Advantages

大数据.png

l This device is based on a 32-bit high performance dual-core processor, internal high speed bus and intelligent I/O ports, and the hardware is in modularized design and can be configured flexibly, featuring interchangeability and easy extension and maintenance.

信息提取.png

l Modularized hardware design makes this relay be easily upgraded or repaired by a qualified service person. Various function optional modules can satisfy various situations according to the different requirements of the users..

可靠服务.png

l The adoption of 16-bit A/D converter and the dual-channel sampling technology can ensure the accuracy and reliability of protection sampling and the correctness of protection operation. It also provides dedicated current transformers for metering, and ensures the high accuracy of telemetering with 48-point high speed sampling rate per cycle.

用户画像.png

l This device can sample the analog values from the traditional instrument transformers, or receive the sampled values from the electronic transformers. It can support the protocol IEC60044-8, IEC61850-9-2 and GOOSE.

信息提取.png

l Various algorithms for protection and measurement have been completed in this device for the feature of electronic transformer sampling, such as the error prevention method of multi-algorithms data anomaly for the digital channels, to realize high accuracy and reliability under various conditions of network faults or communication interruption.

人脸识别.png

l This device has powerful GOOSE functions, and the connection and cooperation between some devices can be realized without using electrical cables, to facilitate the realization of such functions as simple bus differential protection, overload interlock shedding function and backup automatic transfer function etc.

人工智能.png

l This device has fully realized the technology to integrate six functions into one device: protection, measurement, control, remote signaling, merging unit function and remote module functions, to improve the reliability.

信息分享.png

l Various methods of GPS time synchronization are supported in this relay, including SNTP, pulse per second (PPS) and IRIG-B synchronization.

配置管理.png

l The protection modules are completely separated from other modules, and are independent in both hardware and software. The protection functions do not depend on the communication network, so the failure of communication network will not affect the normal operation of the protection functions.

协同文档.png

l Mature protection configuration, fast speed and high security performance can meet the practical requirements. Each protective element is independent, so it is very convenient for whether adopting the selected protective element.

协同文档.png

l Mature protection configuration, fast speed and high security performance can meet the practical requirements. Each protective element is independent, so it is very convenient for whether adopting the selected protective element.

数据挖掘.png

l This device constantly measures and calculates a large amount of analog quantities, such as phase voltage, phase-to-phase voltage, neutral voltage, phase current, neutral current, active power, reactive power, power factor and frequency etc.

数据建模.png

l The human machine interface (HMI) with a small control module (a 240×128-dot LCD, a 9-key keypad and 21 LED indicators) on the front panel is very friendly and convenient to the user.

解决方案.png

l This device can communicate with a SAS or RTU via different communication intermediates: thernet network, RS-485 serial ports. The communication protocol of this device is optional: IEC61850, IEC60870-5-103, DNP3.0 or ModBus.

VR.png

l This device can detect the tripping circuit of the circuit breaker and monitor the operation (close or trip) time of a circuit breaker by checking the auxiliary contacts of the circuit breaker.

意见分析.png

l Complete event recording function is provided: 512 latest protection operation reports, 512 latest supervision records, 128 latest control operation records, 128 latest user operation records and 2000latest records of time tagged sequence of event (SOE) can be recorded.

行业咨询.png

l Powerful fault and disturbance recording function is supported: 64 latest fault or disturbance waves, the duration of a wave recording is configurable.

Specifications/Submodels

Description

IEC 60617

ANSI

CYG Code

Non-directional overcurrent protection

3I>

50/51P

50/51P/51PVT

Directional overcurrent protection

3I> ->

67P

67P

Non-directional earth-fault protection

Io>

50/51N

50/51G/51GVT

Directional earth-fault protection

Io>->

67N

67G

Switch onto fault

SOTF

SOTF

SOTF

Circuit breaker failure protection

3I>/I0>BF

50BF

50BF

Three-phase thermal overload protection

3lth>

49

49F

Phase discontinuity protection

I2/I1>

46PD

46D

Negative sequence current protection

I2>

46N

46N

Three-phase overvoltage protection

3U>

59

59

Positive sequence overvoltage protection

U1>

47

59P

Residual overvoltage protection

Uo>

59G

59G

Negative sequence overvoltage protection

U2>

47

59N

Three phase under voltage protection

3U<

27

27

Positive sequence undervoltage protection

U1<

47

27P

Overfrequency protection

f>

81

81O

Underfrequency protection

f<

81

81URS

Underfrequency restore protection

-

-

81URE

Frequency gradient protection

Df/dt<>

81

81R

Auto-recloser

O ->I

79

79

Synchrocheck

SYNC

25

25SYN

Current circuit supervision

MCS 3I

MCS 3I

CTS

Fuse failure supervision

FUSEF

60

PTS

Trip circuit supervision

TCS

TCM

TCS

Current unbalance protection

dI>C

51NC-1

51NA

Three phase current unbalance protection

3dI>C

51NC-2

51NT

Voltage unbalance protection

PQUUB

PQUUB

59NA

Three phase voltage unbalance protection

PQUUB

PQUUB

59NT

Fault locator

FLOC

21FL

21FL

Three phase under voltage protection of capacitor

3U<

27

CUB_27

Reverse power protection

P>

32R/32O

32R

Voltage Selection

/

/

/

Mechanical Protection



MP

Trip Logic

/

94

94T

Close Logic

/

/

Close Logic

Backup power automatic switch

/

/

BPAS

Wattmetric sensitive earth fault

/

/

SEF